CONSTRUCTION                                                                          
                                                                                      

Basic UPS Topology            On-Line              On-Line                            

                                                                                      

Inverter               Provides 100% load    Provides 100% load                       
                       power 100% of time    power 100% of time                       

Converter              Provides 100% load    Provides 100% load                       
                       power to inverter     power to inverter                        

Bypass Switch          Solid State Static    OPTIONAL Dynamic     Liebert has to be   
                       Switch transfers      (Relay) Switch       severely derated    
                       output between        transfers output     for the most        
                       inverter and input    between inverter     commonly used       
                       utility               and input utility,   electrical          
                                             NOT for all          services            
                                             input/output                             
                                             electrical services                      

Isolation Circuits     5 kHz low pass        Transformer          EPC has increased   
                       filter                                     efficiency and      
                                                                  smaller transients  
                                                                  with smaller,       
                                                                  lighter, and less   
                                                                  expensive hardware  

Internal Batteries     Included              Included                                 


OUTPUT  ELECTRICAL RATINGS                                                            

                                                                                      

Rated power, kVA       @ 250 V               6.0 @ 240 V          EPC provides much   
                       6.0 @ 120/208 V       5.2 @ 120/208 V      more power          

Rated power, kW        4                     4                                        

Phase rated current,   25                    25 @ 240 V                               
A, rms                                                                                

Phase rated current,   75                    75                                       
A peak                                                                                

Neutral rated          33, for 2-phase       Not applicable       EPC can provide     
current, A             output                                     full power on       
                                                                  2-phase output      

Nominal voltages, V    Single Phase: 200;    Single phase: 220;   EPC has universal,  
                       208; 220; 230; 240;   230; 240; with       worldwide output    
                       250;                  modifications Dual   voltages, without   
                       Dual Phase: 100/200;  Phase: 100/200;      field               
                       120/208; 120/240      120/208; 120/240     modifications       

Number of phases       1 or 2                1 or 2                                   

Allowed phase          120; 180; 240         120, 180, no                             
displacements,                               reference to 240                         
degrees                                                                               

Nominal frequencies,   50 or 60              50 or 60                                 
Hz                                                                                    


INPUT  FOR  ELECTRIC  UTILITY                                                         

                                                                                      

Nominal voltages, V    Single Phase: 200;    Single Phase, only   EPC can be powered  
                       208; 220; 230; 240;   208, 240             from                
                       250;                                       100/200-120/208 or  
                       Dual Phase: 100/200;                       240 V electrical    
                       120/208; 120/240                           services. Does not  
                       Same as on the                             need an extra       
                       output                                     transformer in the  
                                                                  external            
                                                                  maintenance bypass  
                                                                  circuit             

Number of phases       1 or 2, Same as       1                    EPC in a 2-phase    
                       output                                     circuit can draw    
                                                                  more power from     
                                                                  the same rated      
                                                                  input service       

Allowed phase          120; 180; 240         Not applicable                           
displacements,                                                                        
degrees                                                                               

Maximum nominal phase  20                    20, cord rated 30 A  EPC does not need   
current, A rms                                                    a higher current    
                                                                  rated electrical    
                                                                  service             

Maximum nominal        20                    Not applicable       EPC does not        
neutral current, A                                                require an          
rms                                                               oversized neutral   
                                                                  conductor           

Overcurrent            25                    No reference                             
protection rating, A                                                                  

Frequency range, Hz    45 - 66               45-65                                    


POWER  CONDITIONING  PERFORMANCE: Voltages between power carrying                                                 
conductors                                                                                                        

                                                                                      

OVER and UNDER VOLTAGES                                                               

                                                                                      

Input voltage range    100 - 275 V           170 - 264 V          EPC can operate at  
                                                                  the extreme high    
                                                                  and low voltages    
                                                                  required for        
                                                                  worldwide           
                                                                  compatibility       

Output voltage         +/- 0.3%              +/-2%                EPC controls to a   
regulation                                                        finer tolerance     
                                                                  using Digital       
                                                                  Signal Processors   
                                                                  (DSPs)              

                                                                                      

FREQUENCY DISTURBANCES                                                                

                                                                                      

Input frequency range  +/- 5 to 6 Hz         +/- 5Hz                                  

Output frequency       Selectable from +/-1  Selectable from                          
range                  to 3 Hz               +/-0.1 to 5 Hz                           

Output                 1 Hz/sec standard,    1 Hz/sec standard,                       
synchronization speed  programmable          programmable                             
(slew rate)                                                                           

                                                                                      

ELECTRICAL NOISE IMMUNITY                                                             

                                                                                      

For Input noise        10 VRMS               No reference                             
amplitude and                                                                         

Input noise frequency  5 kHz - 30 MHz        No reference                             
range                                                                                 

                                                                                      

Output noise           0.5 VRMS              No reference         EPC meets Hewlett   
amplitude                                                         Packard computer    
                                                                  specifications      

In any UPS the attenuation is limited to less than 15 dB between input and output                                                
unshielded power cords in frequency range 450 kHz - 30 MHz                                                                       

                                                                                      
                                                                                      

ELECTRICAL  SURGE  IMMUNITY                                                           

                                                                                      

Input 0.5 us-100 kHz   Output voltage        No reference                             
Ring Wave with         change less than 1%                                            
amplitude 6 kV, 0.5    of nominal                                                     
kA capacity                                                                           

Input 1.2/50 us-8/20   Output voltage        No reference                             
us Combination Wave    change less than 1%                                            
with amplitude 6 kV    of nominal                                                     
and 3 kA capacity,                                                                    
any polarity                                                                          

Input 5/50 ns Fast     Output voltage        No reference                             
Transient Burst with   change less than 1%                                            
peak voltage of 4 kV,  of nominal                                                     
any polarity                                                                          

Input 10/1000 us Wave  Output voltage        No reference                             
with amplitude 780 V   change less than 1%                                            
and 3 kA capacity,     of nominal                                                     
any polarity                                                                          

Input 5 kHz Ring Wave  Output voltage        No reference                             
with amplitude 950 V   change less than 1%                                            
and 2 kA capacity      of nominal                                                     

                                                                                      

ELECTROSTATIC  DISCHARGE  IMMUNITY                                                                 

                                                                                      

Input test voltage 15  Output voltage        No reference                             
kV per IEC 801-2       change less than 1%                                            
                       of nominal                                                     

                                                                                      

ELECTROMAGNETIC FIELD  IMMUNITY                                                       

                                                                                      

Field strength 10V/m   Output voltage        No reference                             
per IEC 1000-4-3       change less than 1%                                            
                       of nominal                                                     


ELECTRICAL  ISOLATION  PERFORMANCE:  Voltages  between  power  carrying                                                        
conductors  and  ground                                                                                                        

                                                                                      

ELECTRICAL  NOISE  IMMUNITY                                                           

                                                                                      

For Input noise        10 VRMS               No reference                             
amplitude and                                                                         

Input noise frequency  5 kHz - 30 MHz        No reference                             
range                                                                                 

                                                                                      

Output noise           0.5 VRMS              No reference         EPC meets Hewlett   
amplitude                                                         Packard computer    
                                                                  specifications      

In any UPS the attenuation is limited to less than 15 dB between input and output                                                
unshielded power cords in frequency range 450 kHz - 30 MHz                                                                       

                                                                                      

ELECTRICAL  SURGE  IMMUNITY: Neutral conductor is grounded at the service                                                       
entrance (USA, Canada, etc.)                                                                                                    

                                                                                      

Input 0.5 us-100 kHz   Output voltage        No reference                             
Ring Wave with         change less than 1%                                            
amplitude 3 kV, 0.1    of nominal                                                     
kA capacity                                                                           

                                                                                      

ELECTRICAL  SURGE  IMMUNITY:  Neutral conductor is NOT grounded at the service                                                   
entrance                                                                                                                         

                                                                                      

Input 0.5 us-100 kHz   Output voltage        No reference                             
Ring Wave with         change less than 1%                                            
amplitude 3 kV, 0.5    of nominal                                                     
kA capacity                                                                           

Input 1.2/50 us-8/20   Output voltage        No reference                             
us Combination Wave    change 30 V peak,                                              
with amplitude 6 kV    0.6 V/usec                                                     
and 3 kA capacity at                                                                  
270 degrees                                                                           


BATTERY  BACKUP  PERFORMANCE                                                          

                                                                                      

Transient output       Output voltage        No reference                             
voltage amplitude      change less than 1%                                            
during transfer from   of nominal                                                     
input AC source to                                                                    
the battery, AC to                                                                    
DC, %                                                                                 

Duration of output     None                  No reference                             
voltage transient, AC                                                                 
to DC, in                                                                             
milliseconds                                                                          

Transient output       Output voltage        No reference                             
voltage amplitude      change less than 1%                                            
during transfer from   of nominal                                                     
the battery to the                                                                    
input source, DC to                                                                   
AC, %                                                                                 

Duration of output     None                  No reference                             
voltage transient, DC                                                                 
to AC, in                                                                             
milliseconds                                                                          

Internal battery       7-12                  10                   Under the same      
reserve time at full                                              conditions          
load, min                                                                             

Internal battery       20 - 30               25                   Under the same      
reserve time at half                                              conditions          
load, min                                                                             

Number of optional     2                     No reference         EPC provides        
battery sets                                                      extended backup     
                                                                  times for long      
                                                                  power failures      

Connector for a user   Standard              No reference                             
supplied battery                                                                      

Recharge time for an   2 hrs. to 100%        2 hrs to 95%         EPC's fast          
internal battery to                                               recharge makes      
nominal reserve time,                                             available backup    
hours                                                             for multiple power  
                                                                  failures in short   
                                                                  time frames         

Recharge time to       2.5 hrs. to 100%      Not available        EPC does not        
nominal reserve time                                              require a separate  
for optional battery                                              charger             
sets, hours                                                                           

Maximum recharge       5                     No reference         EPC's high current  
current for user                                                  makes recharge      
battery, A                                                        faster              

Float voltage          None                  No reference         Absence of float    
                                                                  voltage extends     
                                                                  battery life by     
                                                                  1-2 years           


LOAD  INTERACTION  PERFORMANCE                                                           

                                                                                      

        LOADS                              Linear load power                               
                       factor range:                                                       

                                                                                      

Capacitive-Resistive   From -0 to 1          -.5 to 1             EPC does not need   
                                                                  derating for        
                                                                  capacitive loads    

                                                                                      

Inductive-Resistive    From +0 to 1          +0.5 to 1            EPC does not need   
                                                                  derating for        
                                                                  inductive loads     

Non-linear load crest  ANY                   3                                        
factor                                                                                

                                                                                      

     PERFORMANCE                                                                      

                                                                                      

Output voltage total   5                     5                                        
harmonic distortion                                                                   
(THD) at 100%                                                                         
non-linear load with                                                                  
Crest Factor 3, %                                                                     

Output voltage THD at  3                     3                                        
100% linear load, %                                                                   

Peak voltage           2                     No reference                             
regulation for 100%                                                                   
non-linear loads, %                                                                   

Transient voltage      +/- 8 %               +/-5 %                                   
amplitude under 100%                                                                  
load change                                                                           

Settling time of       10 msec               50 msec                                  
voltage transient                                                                     
under 100% load                                                                       
change                                                                                

Overload handling      Solid State Static    Relay transfer       Liebert will drop   
circuit                Bypass Switch                              sensitive loads     
                                                                  during transfers    
                                                                  because of relay    
                                                                  power interruption  

                                                                                      

Overload capacity      Limited only by the   125% for 10 min,     EPC has the         
                       input circuit         250% for 12 cycles   highest possible    
                       breaker in the                             overload            
                       electric power line                        capability          

Transfer time from     Less than 1 millisec  4 millisec for       Liebert's UPS has   
the inverter to the                          overloads and more   the same transfer   
input AC source                              for faults           time as Standby     
                                                                  UPS (SPS)           

Transfer time from     Less than 1 millisec  4 millisec for       Liebert's UPS has   
the input AC source                          overloads and more   the same transfer   
to the inverter                              for faults           time as Standby     
                                                                  UPS (SPS)           

Laser printer on/off   On inverter, without                                           
handling method        using Static Bypass                                            
                       Switch                                                         

Default power          To the input power    No reference         Output voltage      
connection of the      line by normally                           Mean Time Between   
load                   closed contacts                            Failures is over    
                                                                  100 years           


INPUT  UTILITY  LINE  INTERACTION   PERFORMANCE                                                               

                                                                                      

Input current THD at   5                     5                                        
full load, %                                                                          

Input power factor     Over 0.99             0.98                 Liebert's power     
                                                                  factor data         
                                                                  contradict input    
                                                                  current THD data    

                                                                                      

Startup inrush         25 % of nominal       150% for 3 cycles    EPC does not need   
current                                                           oversized           
                                                                  electrical service  


INSTALLATION  PARAMETERS                                                              

                                                                                      

HxWxD in inches (mm)   28 (711) x 8.25       29 (737) x 9 (229)   Liebert will not    
                       (210) x 24 (610)      x 27 (686)           slide under the     
                                                                  desk                

Weight in lbs (Kg)     225 (101.8)           270 (123)                                

Operating temperature  0 - 40                0 - 40                                   
range, Cº                                                                             

Maximum operating      95%, non-condensing   95 %,                                    
humidity                                     non-condensing                           

Maximum altitude       10,000 (3,000)        4,000 (1,000)        EPC will operate    
without derating, ft                                              without derating    
(m)                                                               in the mountains    

Efficiency at full     92                    85                   EPC provides lower  
load, %                                                           load on air         
                                                                  conditioning,       
                                                                  lower operating     
                                                                  cost                

                                                                                      

Heat generation at     1,250 (365)           2,411 (750)          EPC dissipates a    
full load, BTU/h                                                  half of heat        
(Watts)                                                                               

Cooling method         Forced air            Forced air                               

Audible noise under    55                    55                                       
full load, at 1m                                                                      
distance, dB                                                                          

Location of input      On the FRONT          On the BACK          EPC products are    
power ON/OFF control                                              convenient to       
                                                                  operate             

Input connections      Field wiring          Field wiring                             
                       terminals             terminals                                

Output connections     Field wiring          Field wiring                             
                       terminals             terminals                                

External battery       6-pin AMP connector   Not available                            
connections                                                                           

Grounding              Separate grounding    Separate grounding                       
requirements           conductor             conductor                                

                                                                                      

Maintenance bypass     External two pole     Internal, not for    Liebert's UPS       
switch requirements    make-before-break     all electrical       requires            
                       switch between two    services             additional          
                       pairs of input and                         isolation           
                       output phase                               transformer for     
                       conductors                                 electrical          
                                                                  services not        
                                                                  available with an   
                                                                  internal bypass     

Remote Emergency       Normally open         Available            EPC's low voltage   
Power Off Switch       contact for 12 V, 10                       with reference to   
                       ma signal from UPS,                        ground provides     
                       referenced to ground                       for low cost        
                                                                  wiring              


                                                                                      

DISPLAY                Multifunctional       Multifunctional LCD                      
                       backlit LCD display,  display                                  
                       remaining time to                                              
                       shutdown                                                       

                                                                                      

LOAD  COMPUTER  INTERFACES                                                             

                                                                                      

Interface connectors   One DB-9 with full    Multiple             EPC has simplicity  
                       duplex RS-232                                                  
                       communications and                                             
                       contact closure                                                
                       capabilities                                                   

Compatibility          All software and      None, uses           EPC allows use of   
                       hardware products     proprietary          the most            
                       compatible with       Liebert's software   comprehensive line  
                       Systems Enhancement                        of interface        
                       Corporation                                products for LANs   
                       standards                                                      

RS-232 protocol        Compatible with       Custom, OPTIONAL     EPC uses the        
                       draft UPS Management                       largest MIB         
                       Information Base                           available           
                       (MIB) per RFC 1628                                             
                       by SNMP Research,                                              

                       Inc.                                                           


REGULATORY  COMPLIANCE                                                                      

                                                                                      

        SAFETY                                                                        

                                                                                      

USA UL 1778,           Certified by UL       Certified by UL                          
Uninterruptible Power                                                                 
Supply Equipment                                                                      

CANADA CAN/CSA-C22.2   Certified by UL       Certified by UL                          
No. 107.1-M91                                                                         
Commercial and                                                                        
Industrial Power                                                                      
Supplies                                                                              

International CEI/IEC  Certified by UL, CB   No                                       
950, Safety of         report available                                               
Information                                                                           
Technology Equipment,                                                                 
Including Electrical                                                                  
Business Equipment                                                                    

CENELEC European       Certified by UL, CB   No                                       
Standard EN 50 091-1,  report available                                               
Uninterruptible Power                                                                 
Systems, Part 1,                                                                      
General and Safety                                                                    
Requirements                                                                          

                                                                                      

PERFORMANCE  STANDARDS                                                                 

                                                                                      

International IEC      Certified by UL, CB   No                                       
146-4, Semiconductor   report available                                               
Converters                                                                            

CENELEC European       Certified by UL, CB   No                                       
Standard EN 50         report available                                               
091-3-1,                                                                              
Uninterruptible Power                                                                 
Systems, Part 3-1,                                                                    
General Performance                                                                   
Requirements                                                                          

International IEC 555  Certified by UL       No                                       
and European Standard                                                                 
EN 60 555 -2,                                                                         
Disturbances in                                                                       
Supply Systems Caused                                                                 
by Household                                                                          
Appliances and                                                                        
Similar Equipment,                                                                    
Part 2: Harmonics                                                                     

                                                                                      

ELECTROMAGNETIC  COMPATIBILITY  STANDARDS                                                    

                                                                                      

USA FCC, Part 15,      Certified by UL       Yes                                      
Subpart J, Class A                                                                    

American National      Certified by UL       No reference                             
Standard IEEE                                                                         
C62.41-1991 (option                                                                   
under UL 1449 -                                                                       
Transient Voltage                                                                     
Surge Suppressers)                                                                    
IEEE Recommended                                                                      
Practice on Surge                                                                     
Voltages in                                                                           
Low-Voltage AC Power                                                                  
Circuits                                                                              

CENELEC European       Certified by UL       No                                       
Standard EN 50 091-2,                                                                 
Uninterruptible Power                                                                 
Systems, Part 2, EMC                                                                  
Requirements                                                                          

International IEC      Certified by UL that  No                                       
801-2,                 under the most                                                 
Electromagnetic        severe specified                                               
Compatibility for      Level 4 condition,                                             
Industrial-Process     NORMAL performance                                             
Measurement and        occurs within the                                              
Control Equipment.     specification limits                                           
Part 2: Electrostatic                                                                 
Discharge                                                                             
Requirements                                                                          

International CEI /    Certified by UL that  No                                       
IEC 1000-4-3 (former   under the most                                                 
IEC 801-3), and EN     severe specified                                               
50140,                 Level 3 condition,                                             
Electromagnetic        NORMAL performance                                             
Compatibility; Basic   occurs within the                                              
Immunity Standard;     specification limits                                           
Radiated,                                                                             
Radio-Frequency                                                                       
Electromagnetic                                                                       
Field; Immunity Test                                                                  

International CEI /    Certified by UL that  No                                       
IEC 801-4,             under the most                                                 
Electromagnetic        severe specified                                               
Compatibility for      Level 4 condition,                                             
Industrial-Process     NORMAL performance                                             
Measurement and        occurs within the                                              
Control Equipment.     specification limits                                           
Part 4: Electrical                                                                    
Fast Transient /                                                                      
Burst Requirements                                                                    

International IEC      Certified by UL that  No                                       
801-5 (and CEI),       under the most                                                 
Electromagnetic        severe specified                                               
Compatibility for      Level 4 condition,                                             
Industrial-Process     NORMAL performance                                             
Measurement and        occurs within the                                              
Control Equipment.     specification limits                                           
Part 5: Surge                                                                         
Immunity Requirements                                                                 


Sources: Liebert's specifications and EPC's tentative specifications for 2.5 to 15 kVA DSP UPS products