CONSTRUCTION                                                                          
                                                                                      

Basic UPS Topology            On-Line           Stand-By with     EPC does not need   
                                                Ferroresonant     derating like Best  
                                              Voltage Regulator   for a)              
                                                                  instantaneous       
                                                                  overloads; b)       
                                                                  non-linear loads;   
                                                                  c) capacitive       
                                                                  loads; d)           
                                                                  inductive loads or  
                                                                  special narrow      
                                                                  frequency bands     
                                                                  for backup          
                                                                  generators          

                                                                                      

Inverter               Provides 100% load    Provides 100% load                       
                       power 100% of time    power only during                        
                                             backup                                   

Converter              Provides 100% load    Provides power only                      
                       power to inverter     to charge the                            
                                             battery                                  

Bypass Switch          Solid State Static    No automatic bypass                      
                       Switch transfers      switch                                   
                       output between                                                 
                       inverter and input                                             
                       utility                                                        

Isolation Circuits     5 kHz low pass        Transformer          EPC has increased   
                       filter                                     efficiency and      
                                                                  smaller transients  
                                                                  with smaller,       
                                                                  lighter, and less   
                                                                  expensive hardware  

Internal Batteries     Included              Included in a                            
                                             separate cabinet                         


OUTPUT  ELECTRICAL RATINGS                                                            

                                                                                      

Rated power, kVA       6.25 @ 250 V          7.0                                      

Rated power, kW        4                     5                                        

Phase rated current,   25                    29 @ 240 V                               
A, rms                                                                                

Phase rated current,   75                    No reference                             
A peak                                                                                

Neutral rated          33, for 2-phase       Not applicable       EPC can provide     
current, A             output                                     full power on       
                                                                  2-phase output      

Nominal voltages, V    Single Phase: 200;    Single phase with    EPC has universal,  
                       208; 220; 230; 240;   transformer taps at  worldwide output    
                       250;                  120; 208, 240        voltages            
                       Dual Phase: 100/200;                                           
                       120/208; 120/240                                               

Number of phases       1 or 2                1                    EPC has universal,  
                                                                  worldwide output    
                                                                  phase               
                                                                  configurations      

Allowed phase          120; 180; 240         Not applicable                           
displacements,                                                                        
degrees                                                                               

Nominal frequencies,   50 or 60              60                                       
Hz                                                                                    


INPUT  FOR  ELECTRIC  UTILITY                                                         

                                                                                      

Nominal voltages, V    Single Phase: 200;    Single Phase, 120;   EPC can be powered  
                       208; 220; 230; 240;   208, 240             from                
                       250;                                       100/200-120/208 or  
                       Dual Phase: 100/200;                       240 V electrical    
                       120/208; 120/240                           services. Does not  
                       Same as on the                             need an extra       
                       output                                     transformer in the  
                                                                  external            
                                                                  maintenance bypass  
                                                                  circuit             

Number of phases       1 or 2, same as       1                    EPC in a 2-phase    
                       output                                     circuit can draw    
                                                                  more power from     
                                                                  the same rated      
                                                                  input service       

Allowed phase          120; 180; 240         Not applicable                           
displacements,                                                                        
degrees                                                                               

Maximum nominal phase  20                    35 -65               EPC does not need   
current, A rms                                                    a higher current    
                                                                  rated electrical    
                                                                  service             

Maximum nominal        20                    Not applicable       EPC does not        
neutral current, A                                                require an          
rms                                                               oversized neutral   
                                                                  conductor           

Overcurrent            25                    No reference                             
protection rating, A                                                                  

Frequency range, Hz    45 - 66               57-63                EPC is compatible   
                                                                  with backup         
                                                                  generator service   


POWER  CONDITIONING  PERFORMANCE: Voltages between power carrying                                                 
conductors                                                                                                        

                                                                                      

OVER and UNDER VOLTAGES                                                               

                                                                                      

Input voltage range    100 - 275 V           192 - 276 V @ 240 V  EPC can operate at  
                                             nominal              the extreme of low  
                                                                  voltages required   
                                                                  for worldwide       
                                                                  compatibility       

Output voltage         +/- 0.3%              +/- 3%               EPC controls to a   
regulation                                                        finer tolerance     
                                                                  using Digital       
                                                                  Signal Processors   
                                                                  (DSPs)              

                                                                                      

FREQUENCY DISTURBANCES                                                                

                                                                                      

Input frequency range  +/- 5 to 6 Hz         +/- 3Hz                                  

Output frequency       Selectable from +/-1  Same as input        BEST does not       
range                  to 3 Hz                                    regulate frequency  
                                                                  on the output       

Output                 1 Hz/sec standard     Unavailable                              
synchronization speed                                                                 
(slew rate)                                                                           

                                                                                      

ELECTRICAL NOISE IMMUNITY                                                             

                                                                                      

For Input noise        10 VRMS               No reference                             
amplitude and                                                                         

Input noise frequency  5 kHz - 30 MHz        No reference                             
range                                                                                 

                                                                                      

Output noise           0.5 VRMS              No reference         EPC meets Hewlett   
amplitude                                                         Packard computer    
                                                                  specifications      

In any UPS the attenuation is limited to less than 15 dB between input and output                                                
unshielded power cords in frequency range 450 kHz - 30 MHz                                                                       

                                                                                      
                                                                                      

ELECTRICAL  SURGE  IMMUNITY                                                           

                                                                                      

Input 0.5 us-100 kHz   Output voltage        No reference                             
Ring Wave with         change less than 1%                                            
amplitude 6 kV, 0.5    of nominal                                                     
kA capacity                                                                           

Input 1.2/50 us-8/20   Output voltage        Output voltage       EPC has better      
us Combination Wave    change less than 1%   change less than 2%  surge immunity      
with amplitude 6 kV    of nominal            of nominal                               
and 3 kA capacity,                                                                    
any polarity                                                                          

Input 5/50 ns Fast     Output voltage        No reference                             
Transient Burst with   change less than 1%                                            
peak voltage of 4 kV,  of nominal                                                     
any polarity                                                                          

Input 10/1000 us Wave  Output voltage        No reference                             
with amplitude 780 V   change less than 1%                                            
and 3 kA capacity,     of nominal                                                     
any polarity                                                                          

Input 5 kHz Ring Wave  Output voltage        No reference                             
with amplitude 950 V   change less than 1%                                            
and 2 kA capacity      of nominal                                                     

                                                                                      

ELECTROSTATIC  DISCHARGE  IMMUNITY                                                                 

                                                                                      

Input test voltage 15  Output voltage        No reference                             
kV per IEC 801-2       change less than 1%                                            
                       of nominal                                                     

                                                                                      

ELECTROMAGNETIC FIELD  IMMUNITY                                                       

                                                                                      

Field strength 10V/m   Output voltage        No reference                             
per IEC 1000-4-3       change less than 1%                                            
                       of nominal                                                     


ELECTRICAL  ISOLATION  PERFORMANCE:  Voltages  between  power  carrying                                                        
conductors  and  ground                                                                                                        

                                                                                      

ELECTRICAL  NOISE  IMMUNITY                                                           

                                                                                      

For Input noise        10 VRMS               No reference                             
amplitude and                                                                         

Input noise frequency  5 kHz - 30 MHz        No reference                             
range                                                                                 

                                                                                      

Output noise           0.5 VRMS              No reference         EPC meets Hewlett   
amplitude                                                         Packard computer    
                                                                  specifications      

In any UPS the attenuation is limited to less than 15 dB between input and output                                                
unshielded power cords in frequency range 450 kHz - 30 MHz                                                                       

                                                                                      

ELECTRICAL  SURGE  IMMUNITY: Neutral conductor is grounded at the service                                                       
entrance (USA, Canada, etc.)                                                                                                    

                                                                                      

Input 0.5 us-100 kHz   Output voltage        No reference                             
Ring Wave with         change less than 1%                                            
amplitude 3 kV, 0.1    of nominal                                                     
kA capacity                                                                           

                                                                                      

ELECTRICAL  SURGE  IMMUNITY:  Neutral conductor is NOT grounded at the service                                                   
entrance                                                                                                                         

                                                                                      

Input 0.5 us-100 kHz   Output voltage        No reference                             
Ring Wave with         change less than 1%                                            
amplitude 3 kV, 0.5    of nominal                                                     
kA capacity                                                                           

Input 1.2/50 us-8/20   Output voltage        No reference                             
us Combination Wave    change 30 V peak,                                              
with amplitude 6 kV    0.6 V/usec                                                     
and 3 kA capacity at                                                                  
270 degrees                                                                           


BATTERY  BACKUP  PERFORMANCE                                                          

                                                                                      

Transient output       Output voltage        No reference                             
voltage amplitude      change less than 1%                                            
during transfer from   of nominal                                                     
input AC source to                                                                    
the battery, AC to                                                                    
DC, %                                                                                 

Duration of output     None                  No reference                             
voltage transient, AC                                                                 
to DC, in                                                                             
milliseconds                                                                          

Transient output       Output voltage        No reference                             
voltage amplitude      change less than 1%                                            
during transfer from   of nominal                                                     
the battery to the                                                                    
input source, DC to                                                                   
AC, %                                                                                 

Duration of output     None                  No reference                             
voltage transient, DC                                                                 
to AC, in                                                                             
milliseconds                                                                          

Internal battery       7                     12                                       
reserve time at full                                                                  
load, min                                                                             

                                                                                      

Internal battery       20                    33                                       
reserve time at half                                                                  
load, min                                                                             

                                                                                      

Number of optional     2                     No reference         EPC provides        
battery sets                                                      extended backup     
                                                                  times for long      
                                                                  power failures      

Connector for a user   Standard              No reference                             
supplied battery                                                                      

Recharge time for an   2 hrs to 100%         No reference         EPC's fast          
internal battery to                                               recharge makes      
nominal reserve time,                                             available backup    
hours                                                             for multiple power  
                                                                  failures in short   
                                                                  time frames         

Recharge time to       2.5 hrs. to 100%      No reference         EPC does not        
nominal reserve time                                              require a separate  
for optional battery                                              charger             
sets, hours                                                                           

Maximum recharge       5                     5                                        
current for user                                                                      
battery, A                                                                            

Float voltage          None                  No reference         Absence of float    
                                                                  voltage extends     
                                                                  battery life by     
                                                                  1-2 years           


LOAD  INTERACTION  PERFORMANCE                                                           

                                                                                      

        LOADS                              Linear load power                               
                       factor range:                                                       

                                                                                      

Capacitive-Resistive   From -0 to 1          No reference         EPC does not need   
                                                                  derating for        
                                                                  capacitive loads    

                                                                                      

Inductive-Resistive    From +0 to 1          No reference         EPC does not need   
                                                                  derating for        
                                                                  inductive loads     

Non-linear load crest  ANY                   2.7 to 3.5                               
factor                                                                                

                                                                                      

     PERFORMANCE                                                                      

                                                                                      

Output voltage total   5                     Distortions are      EPC does not need   
harmonic distortion                          very large           any derating for    
(THD) at 100%                                                     non-linear loads    
non-linear load with                                                                  
Crest Factor 3, %                                                                     

Output voltage THD at  3                     5                                        
100% linear load, %                                                                   

Peak voltage           2                     No reference                             
regulation for 100%                                                                   
non-linear loads, %                                                                   

Transient voltage      +/- 8 %               No reference, but                        
amplitude under 100%                         very large                               
load change                                                                           

Settling time of       10 msec               No reference                             
voltage transient                                                                     
under 100% load                                                                       
change                                                                                

Overload handling      Solid State Static    None                                     
circuit                Bypass Switch                                                  

Overload capacity      Limited only by the   125% for 10 min,     EPC has the         
                       input circuit         150% surge           highest possible    
                       breaker in the                             overload            
                       electric power line                        capability          

Transfer time from     Less than 1 millisec  Not applicable                           
the inverter to the                                                                   
input AC source                                                                       

                                                                                      

Transfer time from     Less than 1 millisec  Not applicable                           
the input AC source                                                                   
to the inverter                                                                       

                                                                                      

Laser printer on/off   On inverter, without  Severe output                            
handling method        using Static Bypass   voltage sag                              
                       Switch                                                         

Default power          To the input power    No reference         Output voltage      
connection of the      line by normally                           Mean Time Between   
load                   closed contacts                            Failures is over    
                                                                  100 years           


INPUT  UTILITY  LINE  INTERACTION   PERFORMANCE                                                               

                                                                                      

Input current THD at   5                     No reference, but    EPC does not need   
full load, %                                 large                higher current      
                                                                  capacity input      
                                                                  electrical service  

                                                                                      

Input power factor     Over 0.99             No reference, but    Toshiba's power     
                                             low                  factor data         
                                                                  contradict input    
                                                                  current THD data    

                                                                                      

Startup inrush         25 % of nominal       No reference, but    EPC does not need   
current                                      large                oversized           
                                                                  electrical service  


INSTALLATION  PARAMETERS                                                              

                                                                                      

HxWxD in inches (mm)   28 (711) x 8.25       36.5 (930) x 19      Space saving        
                       (210) x 24 (610)      (485) x 32 (815) -                       
                                             and the same for                         
                                             batteries                                

Weight in lbs (Kg)     225 (102)             578 (274)            EPC's lower weight  
                                                                  reduces shipping    
                                                                  costs and floor     
                                                                  loading             

Operating temperature  0 - 40                0 - 40                                   
range, Cº                                                                             

Maximum operating      95%, non-condensing   95%, non-condensing                      
humidity                                                                              

Maximum altitude       10,000 (3,000)        10,000 (3,000        BEST needs          
without derating, ft                                              operating           
(m)                                                               temperature         
                                                                  derating 1 deg.     
                                                                  Per 1,000 ft.       

Efficiency at full     92                    90 in Stand-By mode                      
load, %                                                                               

                                                                                      

Heat generation at     1,250 (365)           1,896 (556)          EPC dissipates      
full load, BTU/h                                                  less heat           
(Watts)                                                                               

Cooling method         Forced air            Forced air                               

Audible noise under    55                    52                                       
full load, at 1m                                                                      
distance, dB                                                                          

Location of input      On the FRONT          On the BACK          EPC products are    
power ON/OFF control                                              convenient to       
                                                                  operate             

Input connections      Field wiring          Field wiring                             
                       terminals             terminals                                

Output connections     Field wiring          Field wiring                             
                       terminals             terminals                                

External battery       6-pin AMP connector   No reference                             
connections                                                                           

Grounding              Single grounding      Single grounding                         
requirements           conductor             conductor                                

                                                                                      

Maintenance bypass     External two pole     Internal             BEST's UPS          
switch requirements    make-before-break     break-before-make    requires            
                       switch between two                         additional          
                       pairs of input and                         isolation           
                       output phase                               transformer for     
                       conductors                                 120 V output        
                                                                  circuits to use an  
                                                                  external            
                                                                  maintenance bypass  
                                                                  switch              

Remote Emergency       Normally open         Available            EPC's low voltage   
Power Off Switch       contact for 12 V, 10                       with reference to   
                       ma signal from UPS,                        ground provides     
                       referenced to ground                       for low cost        
                                                                  wiring              


                                                                                      

DISPLAY                Multifunctional       Vacuum Fluorescent                       
                       backlit LCD display,                                           
                       remaining time to                                              
                       shutdown                                                       

                                                                                      

LOAD  COMPUTER  INTERFACES                                                             

                                                                                      

Interface connectors   One DB-9 with full    Connector for                            
                       duplex RS-232         RS-232                                   
                       communications and                                             
                       contact closure                                                
                       capabilities                                                   

Compatibility          All software and      None, uses           EPC allows use of   
                       hardware products     proprietary BEST's   the most            
                       compatible with       software             comprehensive line  
                       Systems Enhancement                        of interface        
                       Corporation                                products for LANs   
                       standards                                                      

RS-232 protocol        Compatible with       Custom MIB           Uses the largest    
                       draft UPS Management                       MIB available       
                       Information Base                                               
                       (MIB) per RFC 1628                                             
                       by SNMP Research,                                              
                       Inc.                                                           


REGULATORY  COMPLIANCE                                                                      

                                                                                      

        SAFETY                                                                        

                                                                                      

USA UL 1778,           Certified by UL       Certified by UL                          
Uninterruptible Power                                                                 
Supply Equipment                                                                      

CANADA CAN/CSA-C22.2   Certified by UL       Certified by UL                          
No. 107.1-M91                                                                         
Commercial and                                                                        
Industrial Power                                                                      
Supplies                                                                              

International CEI/IEC  Certified by UL, CB   No                                       
950, Safety of         report available                                               
Information                                                                           
Technology Equipment,                                                                 
Including Electrical                                                                  
Business Equipment                                                                    

CENELEC European       Certified by UL, CB   No                                       
Standard EN 50 091-1,  report available                                               
Uninterruptible Power                                                                 
Systems, Part 1,                                                                      
General and Safety                                                                    
Requirements                                                                          

                                                                                      

PERFORMANCE  STANDARDS                                                                 

                                                                                      

International IEC      Certified by UL, CB   No                                       
146-4, Semiconductor   report available                                               
Converters                                                                            

CENELEC European       Certified by UL, CB   No                                       
Standard EN 50         report available                                               
091-3-1,                                                                              
Uninterruptible Power                                                                 
Systems, Part 3-1,                                                                    
General Performance                                                                   
Requirements                                                                          

International IEC 555  Certified by UL       No                                       
and European Standard                                                                 
EN 60 555 -2,                                                                         
Disturbances in                                                                       
Supply Systems Caused                                                                 
by Household                                                                          
Appliances and                                                                        
Similar Equipment,                                                                    
Part 2: Harmonics                                                                     

                                                                                      

ELECTROMAGNETIC  COMPATIBILITY  STANDARDS                                                    

                                                                                      

USA FCC, Part 15,      Certified by UL       Verified by BEST                         
Subpart J, Class A                                                                    

                                                                                      

American National      Certified by UL       Not clear                                
Standard IEEE                                definition                               
C62.41-1991 (option                                                                   
under UL 1449 -                                                                       
Transient Voltage                                                                     
Surge Suppressers)                                                                    
IEEE Recommended                                                                      
Practice on Surge                                                                     
Voltages in                                                                           
Low-Voltage AC Power                                                                  
Circuits                                                                              

CENELEC European       Certified by UL       No                                       
Standard EN 50 091-2,                                                                 
Uninterruptible Power                                                                 
Systems, Part 2, EMC                                                                  
Requirements                                                                          

International IEC      Certified by UL that  No                                       
801-2,                 under the most                                                 
Electromagnetic        severe specified                                               
Compatibility for      Level 4 condition,                                             
Industrial-Process     NORMAL performance                                             
Measurement and        occurs within the                                              
Control Equipment.     specification limits                                           
Part 2: Electrostatic                                                                 
Discharge                                                                             
Requirements                                                                          

International CEI /    Certified by UL that  No                                       
IEC 1000-4-3 (former   under the most                                                 
IEC 801-3), and EN     severe specified                                               
50140,                 Level 3 condition,                                             
Electromagnetic        NORMAL performance                                             
Compatibility; Basic   occurs within the                                              
Immunity Standard;     specification limits                                           
Radiated,                                                                             
Radio-Frequency                                                                       
Electromagnetic                                                                       
Field; Immunity Test                                                                  

International CEI /    Certified by UL that  No                                       
IEC 801-4,             under the most                                                 
Electromagnetic        severe specified                                               
Compatibility for      Level 4 condition,                                             
Industrial-Process     NORMAL performance                                             
Measurement and        occurs within the                                              
Control Equipment.     specification limits                                           
Part 4: Electrical                                                                    
Fast Transient /                                                                      
Burst Requirements                                                                    

International IEC      Certified by UL that  No                                       
801-5 (and CEI),       under the most                                                 
Electromagnetic        severe specified                                               
Compatibility for      Level 4 condition,                                             
Industrial-Process     NORMAL performance                                             
Measurement and        occurs within the                                              
Control Equipment.     specification limits                                           
Part 5: Surge                                                                         
Immunity Requirements                                                                 


Sources: BEST's specification sheets Model FE7KVA and EPC's tentative specifications for 2.5 to 15 kVA DSP UPS products